FULL-LOAD CURRENT IN AMPERES SINGLE-PHASE ALTERNATING CURRENT MOTORS
| HP |
115V |
200V |
208V |
230V |
| 1/6 |
4.4 |
2.5 |
2.4 |
2.2 |
| 1/4 |
5.8 |
3.3 |
3.2 |
2.9 |
| 1/3 |
7.2 |
4.1 |
4 |
3.6 |
| 1/2 |
9.8 |
5.6 |
5.4 |
4.9 |
| 3/4 |
13.8 |
7.9 |
7.6 |
6.9 |
| 1 |
16 |
9.2 |
8.8 |
8 |
| 1-1/2 |
20 |
11.5 |
11 |
10 |
| 2 |
24 |
13.8 |
13.2 |
12 |
| 3 |
34 |
19.6 |
18.7 |
17 |
| 5 |
56 |
32.2 |
30.8 |
28 |
| 7-1/2 |
80 |
46 |
44 |
40 |
| 10 |
100 |
57.5 |
55 |
50 |
The voltages listed are rated motor voltages.